Stack Analysis
15 ft
Strouhal No. St = 0.20
Critical V 42 mph
Lock-in Risk Moderate
ASCE 7-22 Chapter 29 • Cylindrical Structures

Exhaust Stack & Flue Vortex Shedding Design in Miami-Dade HVHZ

Exhaust stacks and flues in Miami-Dade's High Velocity Hurricane Zone must resist 180 MPH ultimate wind speed while surviving vortex-induced vibration that can destroy an unbraced cylindrical stack in a single storm. The critical design challenge is not just the 60+ psf along-wind pressure but the across-wind resonant oscillation from Von Karman vortex shedding at Strouhal number St = 0.2, which creates alternating lateral forces capable of amplifying displacement by 10 to 40 times the static value when lock-in occurs.

Engineering Alert: A 30-foot, 24-inch diameter exhaust stack at 180 MPH experiences vortex shedding at approximately 19 Hz. If this matches the stack's natural frequency, fatigue failure at the base weld can occur within 4 to 8 hours of sustained hurricane winds. Helical strakes or guy wires are not optional in the HVHZ.
0
Design Wind Speed
0
Strouhal Number
0
Lock-in Amplification
0
Peak Along-Wind Pressure

Von Karman Vortex Street Simulation

Alternating vortex eddies shed from a cylindrical exhaust stack at Strouhal frequency

Shedding Freq
12.4
Hz
Tip Amplitude
0.00
inches
Wind Speed
85
mph
Reynolds No.
4.2E5
subcritical

Along-Wind Drag vs. Across-Wind Vortex Forces on Cylindrical Stacks

Understanding the two fundamentally different wind load mechanisms that exhaust stacks must simultaneously resist in Miami-Dade's 180 MPH design environment.

Along-Wind (Drag) Loading

Along-wind load acts in the direction of the mean wind flow and is calculated using the familiar drag force equation from ASCE 7-22 Chapter 29. For a circular cylindrical stack, the force coefficient Cf ranges from 0.6 to 1.2 depending on aspect ratio (height/diameter), surface roughness, and Reynolds number. At Miami-Dade's 180 MPH ultimate wind speed, the velocity pressure qz at 50 feet above grade in Exposure C reaches approximately 65 psf.

The along-wind force on a 24-inch diameter stack extending 30 feet above the roof is calculated as F = qz × G × Cf × Af, where the gust factor G accounts for dynamic amplification and Af is the projected area. For this example: F = 65 × 0.85 × 0.7 × (2 × 30) = 2,320 lbs of lateral force generating a base moment of approximately 34,800 ft-lbs.

Along-Wind Design Parameters

Force Coefficient (Cf) 0.6 - 1.2
Gust Factor (G) 0.85 - 1.0
qz at 50 ft (180 MPH) ~65 psf
Load Direction Downwind

Across-Wind (Vortex) Loading

Across-wind loading is perpendicular to the mean wind direction and arises from vortex shedding. As air flows around the cylindrical stack, boundary layer separation creates alternating low-pressure vortices on opposite sides. These vortices shed at the Strouhal frequency: f = St × V / D, where St is approximately 0.2 for Reynolds numbers between 300 and 3.5 × 106. The result is a periodic lateral force oscillating at the shedding frequency.

The across-wind force magnitude per unit length is typically only 30 to 50 percent of the along-wind drag at any instant. However, when the shedding frequency matches the stack's natural frequency (lock-in), resonant amplification drives the response 10 to 40 times higher than the static across-wind force. This makes across-wind loading the dominant failure mechanism for slender stacks with height-to-diameter ratios exceeding 10.

Across-Wind Design Parameters

Strouhal Number (St) 0.18 - 0.22
Lock-in Amplification 10x - 40x
Critical Damping 0.2% - 1.5%
Load Direction Cross-wind

Reynolds Number Flow Regimes and Their Effect on Stack Loads

The aerodynamic behavior of cylindrical exhaust stacks changes dramatically across Reynolds number regimes encountered in hurricane wind speeds.

The Reynolds number Re = V × D / ν determines whether the flow around the stack is laminar, turbulent, or in the critical transition zone that causes the drag coefficient to drop sharply. For a 24-inch diameter stack at 180 MPH in standard atmospheric conditions, Re reaches approximately 2.8 × 106, placing it firmly in the post-critical regime. This is significant because the drag coefficient drops from approximately 1.2 in subcritical flow (Re less than 3 × 105) to 0.4 to 0.7 in the post-critical regime. Engineers who use a subcritical Cf value for a stack experiencing post-critical flow at design wind speeds will overestimate along-wind loads by 40 to 100 percent while potentially underestimating across-wind response because vortex coherence changes in post-critical flow.

Flow Regime Reynolds Number Drag Coeff (Cf) Vortex Shedding Design Concern
Subcritical 300 - 3 × 105 1.0 - 1.2 Strong, organized (St = 0.20) High drag + severe vortex shedding
Critical Transition 3 × 105 - 3.5 × 106 0.3 - 0.7 Disrupted, irregular Unpredictable behavior, wide St range
Post-Critical > 3.5 × 106 0.5 - 0.7 Re-established (St = 0.27) Moderate drag, renewed vortex concern
Miami-Dade 180 MPH
(24" stack)
~2.8 × 106 0.5 - 0.8 Critical transition zone Use conservative Cf; check all regimes

Helical Strakes, Shrouds, and Other Vortex Suppression Methods

Engineering countermeasures that break organized vortex shedding and prevent catastrophic lock-in resonance on exhaust stacks in the HVHZ.

Helical Strakes

Three equally-spaced helical fins wrap around the upper one-third of the stack with a height of 0.1D (where D is the outside diameter) and a pitch of 5D. Strakes disrupt vortex correlation along the stack span, reducing across-wind response by 85 to 95 percent. The trade-off is a 20 to 30 percent increase in along-wind drag coefficient because the strakes increase the effective projected area and surface roughness.

  • Strake height: 0.1D from surface
  • Number of strakes: 3 at 120 degrees
  • Pitch: 5D (one full revolution)
  • Coverage: upper 33% of stack height
  • Material: match stack material (316L SS for coastal)
  • Attachment: continuous fillet weld or bolted clamps

Perforated Shrouds

A perforated cylindrical shell surrounds the stack at a gap of 0.1D to 0.15D, with 30 to 40 percent open area from circular or slotted perforations. The shroud disrupts the boundary layer separation point, preventing organized vortex formation. Shrouds reduce across-wind response by 70 to 90 percent with a smaller drag penalty than strakes, typically only 10 to 15 percent.

  • Gap from stack: 0.1D to 0.15D
  • Open area: 30-40% perforated
  • Coverage: upper 40% of stack
  • Weight penalty: 25-35% added
  • Best for: large industrial flues (> 36" dia)
  • Maintenance: inspect annually for blockage

Tuned Mass Dampers

For stacks where external aerodynamic devices are impractical due to thermal or space constraints, an internal tuned mass damper (TMD) adds damping to reduce lock-in amplification. The TMD mass is typically 1 to 5 percent of the generalized mass of the stack's first mode, tuned to the natural frequency with a damping ratio of 5 to 15 percent.

  • Mass ratio: 1-5% of stack generalized mass
  • Frequency tuning: within 5% of fn
  • Added damping ratio: 2-8% effective
  • Response reduction: 50-75%
  • Best for: hot stacks where strakes would fail
  • Requires periodic maintenance and re-tuning

Guy Wire Design for Tall Exhaust Stacks in 180 MPH Wind Zone

Properly engineered guy wires transform a slender, vibration-prone stack into a rigid structure by raising the natural frequency above the critical vortex shedding range.

1

Determine Natural Frequency Without Guys

Calculate the cantilevered natural frequency fn = (1.875)2 / (2πL2) × √(EI/m), where L is stack height, EI is flexural rigidity, and m is mass per unit length. A 30-foot, 24-inch, 14-gauge stainless stack has fn approximately 3.8 Hz cantilevered.

2

Find Critical Wind Speed for Lock-in

Vcr = fn × D / St = 3.8 × 2.0 / 0.2 = 38 mph. This means the stack enters lock-in resonance at just 38 mph, a speed frequently sustained during tropical storms and guaranteed during any hurricane. Lock-in persists over a wind speed range of roughly 0.8 to 1.2 times Vcr.

3

Size Guy Wires and Attachment Height

Attach three guy wires at 120-degree spacing at two-thirds of the stack height (20 feet). Each wire lands at 45 degrees from horizontal, requiring a 20-foot radius from the stack base. Size for the maximum tributary wind force above attachment: for a 180 MPH design, each wire must resist approximately 1,500 lbs tension minimum. Use 3/8-inch galvanized aircraft cable with 14,400 lbs breaking strength providing a safety factor of 4.8 per wire assuming two of three wires loaded.

4

Design Guy Wire Anchors

Roof-mounted anchors require through-bolt connection to structural members with a minimum 5,000 lbs pullout capacity per anchor point. The anchor must resist the vertical and horizontal components of wire tension: V = T × sin(45) = 1,060 lbs uplift, H = T × cos(45) = 1,060 lbs lateral. Anchors embedded in concrete require 3/4-inch Type 316 stainless wedge anchors with 8-inch minimum embedment.

5

Verify Raised Natural Frequency

With guy wires installed, the effective natural frequency rises by a factor of 3 to 8 times the unguyed value, depending on wire pretension and angle. The target is fn(guyed) > St × Vdesign / D = 0.2 × 264 / 2.0 = 26.4 Hz, placing the stack above the vortex shedding frequency at ultimate wind speed.

Guy Wire Material Selection

In Miami-Dade's coastal corrosion environment, standard galvanized cable has a service life of only 8 to 12 years before corrosion reduces cross-section below minimum safety requirements. For exhaust stacks in the HVHZ within 3,000 feet of the coast, specify Type 316 stainless steel wire rope or vinyl-jacketed galvanized cable with stainless thimbles, turnbuckles, and clips. All hardware must be dissimilar-metal-compatible to prevent galvanic corrosion between the wire, fittings, and anchor plate.

  • 3/8" 316SS cable: 12,500 lbs break strength
  • 3/8" galvanized aircraft: 14,400 lbs break
  • Turnbuckle rating: match wire break strength
  • Pre-tension: 10% of wire break strength
  • Inspection interval: 12 months

Common Guy Wire Mistakes

The most frequent engineering errors in guy wire design for HVHZ exhaust stacks include undersizing anchor embedment, ignoring thermal expansion of the stack that changes wire tension seasonally, using dissimilar metals that corrode galvanically, and failing to account for the dynamic amplification factor when sizing wires for across-wind loading.

  • Anchor in roof membrane only (no structural tie)
  • Galvanized wire to stainless turnbuckle (galvanic)
  • No initial pretension (wire goes slack in service)
  • Wire angle too steep (> 60 degrees from horizontal)
  • No vibration damper on long wire spans

Base Plate and Anchor Bolt Design for Stack Wind Moment

The base plate connection transmits the full wind overturning moment and shear into the building structure, making it the critical failure point for exhaust stack systems.

Base Plate Sizing

The base plate distributes the concentrated wind moment from the stack into a bearing area on the roof curb or structural support. For a 24-inch diameter stack experiencing a base moment of 34,800 ft-lbs from 180 MPH along-wind loading (and potentially double that from across-wind lock-in), the base plate must be large enough to develop the anchor bolt pattern and stiff enough to prevent prying action that amplifies bolt forces.

Minimum base plate thickness for a 4-bolt pattern on a 24-inch stack is typically 3/4 inch for A36 steel or 5/8 inch for A572 Grade 50. The bolt circle diameter should be at least 1.5 times the stack outside diameter. For severe across-wind conditions, an 8-bolt pattern on a bolt circle of 36 inches is recommended, with each bolt sized for the combined tension from overturning and prying plus shear from base shear force.

Anchor Bolt Engineering

Anchor bolts for HVHZ exhaust stacks must resist simultaneous tension (from overturning moment and wind uplift) and shear (from lateral wind force). Using ACI 318 Chapter 17 for post-installed anchors in concrete or manufacturer-specific ESR reports for proprietary systems, each bolt in the tension zone of the base plate carries T = M / (n/2 × dbc) plus any direct uplift, where n is the bolt count, and dbc is the bolt circle diameter.

For the example 30-foot stack with 34,800 ft-lbs base moment on 4 bolts at a 30-inch bolt circle, each tension bolt carries approximately 13,920 lbs. Using 3/4-inch A325 anchor bolts (allowable tension of 19,200 lbs at ultimate), the demand-capacity ratio is 0.73 for along-wind alone. Adding across-wind lock-in forces can double the moment, pushing demand to 0.73 × 2.0 = 1.46, which exceeds capacity and requires either larger bolts, more bolts, or vortex suppression.

Kitchen Exhaust Stacks vs. Industrial Flues: Design Differences

While both penetrate the roof and face the same 180 MPH wind speed, the engineering complexity between a restaurant kitchen exhaust and an industrial boiler flue differs by an order of magnitude.

Parameter Kitchen Exhaust Industrial Flue Design Impact
Typical Diameter 12 - 24 inches 24 - 96 inches Larger diameter = lower shedding freq
Height Above Roof 6 - 15 feet 20 - 80 feet Taller = higher moment, lower fn
Operating Temperature 150 - 400 °F 500 - 1,200 °F High temp reduces steel yield strength
Wall Construction Double-wall insulated Refractory-lined steel Heavy lining changes dynamic mass
Vortex Shedding Risk Low (short, stiff) High (tall, slender) Industrial flues nearly always need analysis
Thermal Expansion Minor (0.1 - 0.3 in) Significant (1 - 4 in) Expansion joints interact with wind bracing
HVHZ Approval Path Prescriptive or PE letter Full structural analysis required Industrial flues always need PE certification
Guy Wire Need Rarely (H/D < 10) Usually (H/D > 10) Critical for slenderness ratios over 10

🍴 Kitchen Exhaust Specifics

Restaurant kitchen exhaust stacks in Miami-Dade typically rise 6 to 12 feet above the roofline with diameters of 12 to 24 inches, giving height-to-diameter ratios below 8. At this slenderness, the cantilevered natural frequency exceeds 15 Hz, and the critical wind speed for vortex lock-in is above 100 mph for a 12-inch diameter stack. While vortex shedding still occurs, the dynamic amplification remains modest because the damping provided by the double-wall construction and the grease-laden airstream absorbs energy.

The primary wind load concern for kitchen exhaust stacks is the static along-wind force and the overturning moment at the roof curb penetration. The roof curb flashing must resist both the uplift from negative roof pressure at corners and edges and the moment from the stack's wind force. A 12-foot, 18-inch kitchen exhaust stack at 180 MPH generates roughly 850 lbs of lateral force and 5,100 ft-lbs of base moment, manageable with a standard 4-bolt curb connection using 5/8-inch anchor bolts.

Industrial Flue Specifics

Industrial flues serving boilers, generators, or process equipment in Miami-Dade present the full spectrum of wind engineering challenges. A 48-inch diameter refractory-lined steel flue rising 50 feet above the rooftop has a height-to-diameter ratio of 12.5, placing it squarely in the vortex-shedding-critical range. The cantilevered natural frequency drops to approximately 1.5 to 2.5 Hz, with critical wind speed Vcr = 2.5 × 4.0 / 0.2 = 50 mph, well within tropical storm range.

Operating temperatures of 800 to 1,200 degrees Fahrenheit reduce the yield strength of A36 steel by 25 to 60 percent and introduce thermal expansion of 2 to 4 inches over the stack height. Expansion joints necessary for thermal relief create weak points that cannot transfer wind moment, requiring the wind lateral system to span across or bypass these joints. The refractory lining adds significant mass (40 to 80 lbs per linear foot) that lowers the natural frequency further, increasing vulnerability to vortex lock-in during the initial wind speed ramp of a hurricane approach.

Roof Penetration Flashing and Stack Cap Wind Uplift

The interface between exhaust stack, roof membrane, and rain cap is a convergence of three separate wind load paths that must be resolved without compromising waterproofing.

Roof Penetration Flashing

Exhaust stack roof penetrations in Miami-Dade HVHZ sit in roof zones where negative pressure (suction) is highest, particularly within 10 percent of the building dimension from edges and corners. ASCE 7-22 Figure 30.3-2A assigns GCp values as negative as -2.8 for small tributary areas in corner zones. For a 24-inch stack penetration with a 36-inch square base flashing, the effective tributary area is only 9 square feet, placing it in the highest negative pressure category.

The base flashing must resist uplift of qz × GCp = 65 × 2.8 = 182 psf on the flashing plate, totaling 1,638 lbs of uplift on the 9 square-foot base. This force transfers through the flashing counter-flashing system into the roof curb, which must be anchored to the structural deck with capacity exceeding this uplift plus the stack's overturning contribution. Using 5/8-inch expansion anchors at 8 inches on center around the curb perimeter, each anchor carries approximately 200 lbs of the distributed uplift.

Stack Cap and Rain Cap Loads

Stack caps and rain caps at the top of exhaust stacks create a bluff body that experiences different wind forces than the cylindrical shaft below. A conical rain cap with a 30-inch diameter on a 24-inch stack has a force coefficient of 0.8 to 1.3 depending on the cone angle and gap between cap and stack. At 180 MPH, the cap alone experiences 350 to 570 lbs of lateral force plus 150 to 300 lbs of uplift from the Bernoulli effect as wind accelerates over the conical surface.

Cap attachment must resist these forces through the bolted or welded connection to the stack wall. A common failure mode is cap departure during hurricanes, when the combined uplift from wind suction and the lateral moment from drag tear the cap free. Lost caps allow rain and debris intrusion into the exhaust system, potentially flooding mechanical equipment below. In the HVHZ, cap connections should be designed for 1.5 times the calculated wind force as a safety margin against dynamic gust effects at the stack tip where turbulence intensity is highest.

Coastal Corrosion and Thermal Degradation of Stack Wind Resistance

Miami-Dade's salt-laden marine atmosphere and the extreme thermal cycling of exhaust stacks create a compound degradation mechanism that erodes wind load capacity every year the stack is in service.

Atmospheric Corrosion Rates

Carbon steel exhaust stacks within 1,500 feet of the Miami-Dade coastline experience corrosion rates of 8 to 15 mils per year on exterior surfaces directly exposed to salt spray. Interior surfaces exposed to flue gases containing sulfur compounds or moisture corrode at 3 to 8 mils per year. Over a 20-year service life, a 14-gauge (0.075-inch) carbon steel stack can lose 30 to 60 percent of its wall thickness, reducing the section modulus and moment of inertia that directly govern wind bending resistance.

  • 0-1,500 ft from coast: 8-15 mils/year
  • 1,500-5,000 ft: 3-8 mils/year
  • 5,000+ ft inland: 1-3 mils/year
  • Interior (wet flue): 3-8 mils/year

Thermal Effects on Steel

Elevated exhaust temperatures reduce the yield strength and elastic modulus of steel, directly impacting the stack's capacity to resist wind loads during operation. At 600 degrees Fahrenheit, A36 steel retains approximately 77 percent of its room-temperature yield strength. At 1,000 degrees, retention drops to approximately 42 percent. This means an industrial flue operating at 1,000 degrees has barely half the wind bending capacity of the same stack at ambient temperature.

  • 400°F: 92% yield retention
  • 600°F: 77% yield retention
  • 800°F: 58% yield retention
  • 1,000°F: 42% yield retention
  • Elastic modulus also drops proportionally

Material Selection for HVHZ

The Florida Building Code requires that corrosion be accounted for in the 50-year design life of structural components. For HVHZ exhaust stacks, the practical material options each carry trade-offs between corrosion resistance, high-temperature performance, cost, and weldability.

  • Type 316L SS: best coastal corrosion resistance, good to 1,500°F, 3x cost of carbon steel
  • Type 304L SS: good corrosion resistance, good to 1,500°F, 2.5x cost
  • AL-6XN (super austenitic): premium coastal, 4x cost
  • Carbon steel + 20-mil coating: economical, recoat every 10 years
  • Aluminum (6061-T6): lightweight, no use above 400°F

Need Exhaust Stack Wind Load Calculations?

Get ASCE 7-22 compliant wind loads for cylindrical stacks, flues, and rooftop equipment in Miami-Dade HVHZ. Along-wind drag and across-wind vortex analysis included.

Calculate Stack Loads Now →

Frequently Asked Questions: Exhaust Stack Wind Loads in Miami-Dade

Vortex shedding is the alternating release of low-pressure vortices from opposite sides of a cylindrical stack as wind flows around it, creating a periodic lateral force called the Von Karman vortex street. The shedding frequency follows f = St × V / D where St is approximately 0.2. In Miami-Dade HVHZ with 180 MPH design wind speed, a 24-inch stack sheds vortices at roughly 19 Hz at ultimate. If this frequency coincides with the stack's natural frequency (lock-in), resonant oscillation amplifies lateral deflections by 10 to 40 times the static displacement, causing fatigue cracking at the base weld within hours of sustained wind. Even at lower, more sustained wind speeds of 80 to 120 MPH during a hurricane's inner bands, smaller stacks with lower natural frequencies can experience lock-in that persists for extended durations.
Helical strakes are three equally-spaced fins spiraling around the upper third of a stack, each protruding 0.1D from the surface with a pitch of 5D. They disrupt the organized vortex shedding pattern and break the correlation of vortex release along the stack height. This eliminates the coherent lateral forcing that causes lock-in resonance, reducing across-wind response by 85 to 95 percent. Strakes increase along-wind drag by approximately 20 to 30 percent, but this penalty is minor compared to the catastrophic across-wind amplification they prevent. For Miami-Dade HVHZ stacks taller than 15 feet, strakes are strongly recommended because the wide range of wind speeds during a hurricane approach virtually guarantees that the shedding frequency will pass through the stack's natural frequency at some point during the event.
Rooftop exhaust stacks fall under ASCE 7-22 Chapter 29 for other structures and building appurtenances. Force coefficients come from Table 29.4-1 for chimneys and similar cylindrical structures, with Cf values of 0.8 to 1.2 depending on cross-section shape, aspect ratio, and surface roughness. Velocity pressure uses the 180 MPH ultimate wind speed at the stack top elevation with appropriate exposure category. The across-wind vortex shedding response must be evaluated per Chapter 29.4 commentary. The Florida Building Code 2023 adopts ASCE 7-22 with Miami-Dade local amendments requiring product approval or engineering certification for all rooftop penetrations. Stacks exceeding 15 feet above the roof or 24 inches in diameter generally require a signed and sealed structural analysis from a Florida-licensed Professional Engineer.
Guy wires for HVHZ exhaust stacks use three or four cables equally spaced at 120 or 90 degrees, attached at two-thirds of stack height. Each wire must resist both along-wind and across-wind forces at 180 MPH. For a 30-foot, 18-inch stack, each wire typically requires minimum 3/8-inch galvanized aircraft cable with 14,400 lbs breaking strength. Wire anchors connect to structural roof members with minimum 5,000 lbs pullout capacity per point. The critical design goal is raising the stack's natural frequency above the vortex shedding frequency at design wind speed, which for this example means fn(guyed) must exceed 26 Hz. All hardware must be Type 316 stainless steel or hot-dip galvanized for coastal corrosion resistance, and wires require 10 percent pre-tension to prevent slack under service conditions.
Kitchen exhaust stacks are typically 12 to 24 inches diameter, 6 to 15 feet above the roofline, and operate at 150 to 400 degrees Fahrenheit. Their short, stiff geometry usually means the natural frequency is high enough that vortex lock-in is unlikely. Static wind load analysis per ASCE 7-22 Chapter 29 is usually sufficient, and a prescriptive compliance path may be available. Industrial flues range from 24 to 96 inches diameter, extend 20 to 80 feet, and operate at 500 to 1,200 degrees that significantly reduce steel strength. Their tall, slender geometry makes vortex lock-in almost certain during hurricane approach wind speeds. Full dynamic analysis, vortex suppression devices, thermal expansion accommodation, and Florida PE certification are required. The engineering effort for an industrial flue can be 10 to 20 times that of a kitchen exhaust stack.
Coastal corrosion in Miami-Dade progressively reduces wind resistance by thinning steel walls, degrading anchor bolts, and weakening welds. A carbon steel stack within 3,000 feet of the coast loses 5 to 10 mils of wall thickness annually, translating to 15 to 30 percent section modulus reduction over 20 years for a 14-gauge stack. This directly reduces bending capacity at the critical base section where wind moment peaks. The FBC requires corrosion allowance of typically 1/16 inch extra wall thickness and specifies that severe marine environment stacks use Type 304L or 316L stainless steel, aluminum alloy, or marine-grade coated carbon steel rated for 20-plus year service. Anchor bolt corrosion is equally critical: a 3/4-inch bolt losing 1/16 inch of diameter from corrosion loses roughly 15 percent tensile capacity, potentially dropping below the required wind load resistance before end of service life.

Get Your Exhaust Stack Wind Analysis

ASCE 7-22 compliant calculations for cylindrical stacks, flues, and rooftop penetrations in Miami-Dade's 180 MPH High Velocity Hurricane Zone.

Start Calculation → View All Calculators